1. Application
AM1 series moulded case circuit breaker is one of products developed and manufacturedby adopting international advanced technology. It is supplied witd rated insulating voltage 800V and used for circuit of A.C. 50Hz, rated operating voltage AC 400V (or below), rated operating current up to 800A for infrequent changing over and starting of tde motors.tde products conforms to IEC60947-2 standard.

2. Main Technical Specification
Table1
Type Rated
current
(A)
Pole num-ber Rated insui-ating volt
-age
(V)
Rated operat-ing
volt-
age
(V)
Arcing-over distance (mm) Ultimate short
circuit breaking capacity (KA)
Servies short
circuit breaking capacity
Operation perform-
ance
Utiliza-
tion
cat-
egory
Load Unload
AM1-63L (6),10,16,20, 25,32,40,50,63 3,4 500V 400V 0 25 18 1500 8500 A
AM1-63M 0 50 35
AM1-100L (10),16,20,25,
32,40,50,63,
80,100
800V 0(≤ 50) 35 22
AM1-100M 0(≤50) 50 35
AM1-100H 0(≤50) 85 50 1000 7000
AM1-225L 100,125,160, 180,200,225 ≤50 35 22
AM1-225M ≤50 50 35
AM1-225H ≤50 85 50 1000 4000
AM1-400L 225,250,315, 350,400 ≤50 50 35
AM1-400M ≤100 65 42
AM1-630L 400
500
630
≤100 50 35
AM1-630M ≤100 65 42
AM1-630H ≤100 100 65
AM1-800M 630,700,800 3 ≤100 75 50
AM1-800H ≤100 100 65
AM1-1250M 1000,1250 ≤100 100 65
AM1-1250H ≤100 125 75
Note: 6A no tdermal protection
tde N-pole of four-poles breaker is sifed at tde right side of tde product has four types:
Type A: No current trip-lease on N pole which making all tde time, not closing and opening witd tde otder tdree poles.
Type B: No current trip-release on N pole which closing and opening witd tde otder poles.
Type C: Witd current trip-release which closing and opening witd tde otder tdree poles.
Type D: Witd current frip-release which making all tde time not closing and opening witd tde otder tdree poles.

3. Protection Characteristic
The thermodynamic release of a circuit breaker provides the feature of inverse time-delay, while the magnetic release is the instantaneous operation as shown on table 2(distribution circuit breaker) and table 3 (motor protection circuit breaker).