tdermodynamic release( ambient temp land +40°C marine +45°C )
Operational
current of
magnetic
release (A)
1.05In(cold state)
Inoperative time(h)
1.30In(heat state)
Operative time(h)
10 ≤ In ≤ 63
≥ 1
< 1
10In?0%
63 < In ≤ 100
≥ 2
< 2
100 < In ≤ 800
≥ 2
< 2
5In?0% 10In?0%
Table 3
Rated Current of Release (A)
tdermodynamic Release ( ambient temp land +40°C marine +45°C )
Operational Current of Magnetic Release (A)
1.0In(cold state) Inoperative time(h)
1.20In(heat state) Operative time (h)
1.50In(heat state) Operative time (h)
7.2In(cold state) Operative time(h)
10 ≤ In ≤ 225
≥ 2
< 2
≤ 4min
4s < Tp ≤ 10s
12In?0%
225 < In ≤ 630
≤ 8min
6s < Tp ≤ 20s
4. Accessories of Circuit breaker 4.1 The external accessories of the breaker · Motor-driven operation device 1) Wiring diagram of type CDM electromagnetic operation device(fitting AM1-63,100,225) see the following drawing (wiring diagram of the external accessories of the breaker in the dotted frame)
Code description: SB1‚SB2 stand for push button.(provided by users themselves) Number "1"‚"2"‚"3"stand for number of wiring terminals.
Voltage rating: AC50Hz 230V‚400V,DC 220V
2) Wiring diagram of type CD motor-driven operation device (fitting AM1-400‚630‚800) see belows (wiring diagram of the external accessories of the breaker in the dotted frame)
Code description: SB1‚SB2 stand for push button.(provided by users themselves)"X"stands for line connection terminals
Voltage rating: AC50Hz 230V‚400V;DC220V