AM2-630N/4P |
Flashing at 105% or more of Ir setting threshold
| Type |
Rated current In(A) |
Note |
| AM2-100 |
40‚100 |
Ir=0.4…1 × In(adjustable 48 setting)
Tripping between 1.05…1.3 × Ir (IEC60947-2)
(Long-time overload protection)
Im=2-3-4-5-6-7-8-10 × Ir
(Short-circuit protection) |
| AM2-160 |
40‚100‚160 |
| AM2-250 |
40‚100‚160‚250 |
AM2 22ME: protection of motor for AM2-100\160\250
1. Overload protection with adjustable threshold, as defined by IEC60947-4 (2) tripping class 10
2. Short-circuit protection with fixed threshold (13xIr)
3. phase failure protection (tripping time delay between 3.5s-6s)
4. Load indication : dark less than 105% of Ir setting threshold;
Flashing at 105% or more of Ir setting threshold
| Type |
Rated currentIn(A) |
Note |
| AM2-100 |
40‚50‚80‚100 |
Ir=0.6-0.63-0.67-0.71-0.75-0.80-0.85-0.90-0.95-1 × In |
| AM2-160 |
40‚50‚80‚100‚150 |
| AM2-250 |
40‚50‚80‚100‚150‚220 |
AM2 23SE: protection of low-voltage distribution networks for AM2-400\630
1. Overload protection with adjustable threshold
2. Short-circuit protection with adjustable threshold
3. Load indication : light at 90% of Ir setting threshold;
Flashing at 105% or more of Ir setting threshold |