  AM2 Series Moulded Case Circuit Breaker

  AM2 43ME: protection of motor for AM2-400\630


1. Overload protection with adjustable threshold, as defined by IEC60947-4 (2) tripping class 10A,10 and 20
2. Short-circuit protection with adjustable threshold (6…13xIr)
3. Phase failure protection (built-in electronic release: operates unbalanced single-phase currentat 40% and more than)(tripping time delay 4s±10%),as defined by IEC60947-4.1
4. Load indication : Flashing more than Ir setting threshold
5. Fault indication
LEDs indicates the type of fault that caused tripping
Overload (LT protection) or abnormal component temperature (>Ir);
Short-circuit (ST or instantaneous protection)( >Im);
Phase failure (right LED);
Microprocessor malfunction ( (>Ir) ( >Im) and phase failure LEDs all go on )
Battery powered. Spare battery are supplied in an adapter box. When a fault occurs ,the LEDindicating the type of fault ,lights for about 10 minutes. The information is however stored inmemory.The LED can be illuminated by pressing the test pushbutton. The LED automaticallygoes off and the memory is cleared when the circuit breaker is reset.

Type Rated current In(A) Note
AM2-400 400 Ir=0.4…1 × In(adjustable 48 setting)
Trip degree: class 10A,10,20(IEC60947-4)
(Long-time overload protection)
Im=6-7-8-9-10-11-12-13 × Ir
(Short-circuit protection)
AM2-630 630
Under voltage release,Shunt release
Under voltage release
Shunt release

4. Accessories


Auxiliary Contact,Alarm contact
Auxiliary Contact
Alarm contact