AM3-400L/3P
|
Table 2
| Type |
Thermal magnetic release |
Electronic release |
| Rated current In(A) |
Note |
Rated current In(A) |
Note |
| AM3-125 |
12.5,16,20,25,32,40, 50,63,80,100,125 |
T fixed M fixed |
- |
|
| AM3-160 |
16,20,25,32,40,50, 63,80,100,125,160 |
T adjustable (0.7~1In) M fixed |
- |
|
| AM3-250 |
100,125,160,180, 225,250 |
T adjustable (0.7~1In) M fixed |
- |
|
| AM3-400 |
225,250,315, 350,400 |
T fixed or adjustable (0.7~1In) M fixed |
320,400 |
I1=0.4…1 ×In AM3 PR211(L-LI) I1=0.4…1 × In AM3 PR212(LSI-LSIG) Tripping between 1.05…1.3 × I1 (IEC60947-2) I2t=constant (Long-time overload protection) I2=1-2-3-4-6-8-10 × In t2=0.05s, 0.1s, 0.25s, 0.5s adjustable (Short-circuit short time delay protection) I3=1.5-2-4-6-8-10-12 × In (Instantaneous short-circuit protection) I4=0.2-0.3-0.4-0.6-0.8-0.9-1 × In t4= 0.1s, 0.2s, 0.4s, 0.8s adjustable (Earth fault protection) |
| AM3-630 |
400,500,630 |
T fixed M fixed |
630 |
| AM3-800 |
630,700,800 |
T fixed M fixed |
800 |
| AM3-1250 |
- |
- |
800,1000, 1250 |
| AM3-1600 |
- |
- |
1000,1250, 1600 |
Note: T-thermal M-magnetic L-long time S-short time relay I-instantaneous G-earth fault AM3-125/160 In=12.5,16,20,32,40 magnetic protection that is fixed at 500A.
4. Accessories
4.1 The external accessories of the breaker · Motor-driven operation device
1) Wiring diagram of type CDM electromagnetic operation device(fitting AM3-125,160,250) see the following drawing (wiring diagram of the external accessories of the breaker in the dotted frame)
Code description: SB1‚SB2 stand for push button.(provided by users themselves)
Number "1" ‚"2"‚"3" stand for number of wiring terminals.
Voltage rating: AC50Hz 230V‚400V, DC 220V
2) Wiring diagram of type CD motor-driven operation device (fitting AM3-400‚630‚800) see belows (wiring diagram of the external accessories of the breaker in the dotted frame) |