 Motor-driven operation device |
Code description: SB1‚SB2 stand for push button. (provided by users themselves) "X" stands for line connection terminals
Voltage rating: AC50Hz 230V‚400V; DC220V
· Rotary handle Economic extended rotary handle Degree of protection:IP30 Function: 1) With indication of isolation
2) Indication of three positions 0(off) I(on) and tripped
3) Door opening prevented when circuit breaker is on
4.2 The internal accessories of the breaker · Undervoltage release Us: AC50/60Hz 400V, 230V When the operation voltage is 35%~70% of the rated voltage, the under-voltage release should make the breaker trip correctly. When the operation voltage is 85%~110% of the rated voltage, the under-voltage release should make the breaker close. In case of the operation voltage less than 35% of the rated voltage, the under-voltage should prevent the breaker from closing. Note: Only the under-voltage release should be energized in advanced, the breaker could be recramped and turned-on, otherwise the breaker will be damaged.
· Shunt release Us: AC50/60Hz 400V 230V; DC110V 220V The shunt release should make the breaker trip reliably when the operation voltage is 70%~110% of the rated control voltage
· Auxiliary Contact
| When the breaker is in "off" |
 |
Size
2N/O+2N/C
1N/O+1N/C |
 |
| When the breaker is in "on" |
When the breaker is in "off", the contacts switch from "close" to "open".
When the breaker is in "off", the contacts switch from "open" to "close" |
|