| Inm(A) |
Long time-delay |
Short time-delay |
Instantaneous |
Earthing failure |
| Ir1 |
Error |
Ir2 |
Error |
Ir3 |
Error |
Ir4 |
Error |
| ≥ 2000 |
(0.4~1)In |
±10% |
(0.4~15)In |
±10% |
1.0In~15kA |
±15% |
Inm ≤ 4000A(0.2-0.8) In
(Max.1200A.Min.200A)
Inm ≤ 6300A(0.2-1.0) In |
± 10% |
Note: 1.When the breaker could realize over-load with long time delay .short-circuit with short time-delay and short-circuit instantaneous protections, the setting ratings can not be over-lapped ,and Ir1< Ir2< Ir3