CJX2-D09 |
1. Application
CJX2 series AC Contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz or 60Hz, rated current up to 620A, for making, breaking, frequently starting & controlling the AC motor. Combined with the auxiliary contact block, timer delay & machine-interlocking device etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta starter. With the thermal relay, it is combined into the electromagnetic starter. The product conforms to IEC60947-4-1 stardand.
2. Specification
| Type |
CJX2-
D09 |
CJX2-
D12 |
CJX2-
D18 |
CJX2-
D25 |
CJX2-
D32 |
CJX2-
D40 |
CJX2-
D50 |
CJX2-
D65 |
CJX2-
D80 |
CJX2-
D95 |
Rated working
current (A) |
AC3 |
9 |
12 |
18 |
25 |
32 |
40 |
50 |
65 |
80 |
95 |
| AC4 |
3.5 |
5 |
7.7 |
8.5 |
12 |
18.5 |
24 |
28 |
37 |
44 |
Standard
power ratings
of 3-phase motors
50/60Hz in
category AC-3 |
220/230V |
2.2 |
3 |
4 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
25 |
| 380/400V |
4 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
| 415V |
4 |
5.5 |
9 |
11 |
15 |
22 |
25 |
37 |
45 |
45 |
| 500V |
5.5 |
7.5 |
10 |
15 |
18.5 |
22 |
30 |
37 |
55 |
55 |
| 660/690V |
5.5 |
7.5 |
10 |
15 |
18.5 |
30 |
33 |
37 |
45 |
55 |
| Rated heat current (A) |
20 |
20 |
32 |
40 |
50 |
60 |
80 |
80 |
125 |
125 |
| Electrical life |
AC3 (x104) |
100 |
100 |
100 |
100 |
80 |
80 |
60 |
60 |
60 |
60 |
| AC4 (x104) |
20 |
20 |
20 |
20 |
20 |
15 |
15 |
15 |
10 |
10 |
| Mechanical life (x104) |
1000 |
1000 |
1000 |
1000 |
800 |
800 |
800 |
800 |
600 |
600 |
| Number of the contacts |
3P+NO |
3P+NC+NO |
| 3P+NC |
| Type |
CJX2-D115 |
CJX2-D150 |
CJX2-D170 |
CJX2-D205 |
CJX2-D245 |
CJX2-D300 |
CJX2-D410 |
CJX2-D475 |
CJX2-
D620 |
Rated working
current (A) |
AC3 |
115 |
150 |
170 |
205 |
245 |
300 |
410 |
475 |
620 |
| AC4 |
52 |
60 |
75 |
85 |
105 |
117 |
138 |
147 |
180 |
Standard
power ratings
of 3phase motors
50/60Hz in
category AC-3 |
220/230V |
30 |
40 |
55 |
63 |
75 |
100 |
110 |
147 |
200 |
| 380/400V |
55 |
75 |
90 |
110 |
132 |
160 |
220 |
265 |
335 |
| 415V |
59 |
80 |
100 |
110 |
132 |
180 |
220 |
280 |
375 |
| 500V |
75 |
90 |
110 |
129 |
160 |
200 |
250 |
355 |
400 |
| 660/690V |
80 |
100 |
110 |
129 |
160 |
220 |
280 |
355 |
450 |
| Rated heat current (A) |
200 |
250 |
250 |
275 |
315 |
400 |
500 |
700 |
1000 |
| Electrical life |
AC3 (x104) |
200 |
60 |
60 |
50 |
50 |
50 |
30 |
30 |
20 |
| AC4 (x104) |
15 |
15 |
15 |
15 |
15 |
15 |
8 |
8 |
5 |
| Mechanical life (x104) |
300 |
300 |
300 |
300 |
300 |
300 |
100 |
100 |
100 |
3. Standard Control Circuit Voltage
| Volts |
24 |
42 |
48 |
110 |
220 |
230 |
240 |
380 |
400 |
415 |
440 |
500 |
660 |
| 50Hz |
B5 |
D5 |
E5 |
F5 |
M5 |
P5 |
U5 |
Q5 |
V5 |
N5 |
R5 |
S5 |
Y5 |
| 60Hz |
B6 |
D6 |
E6 |
F6 |
M6 |
? |
U6 |
Q6 |
? |
? |
R6 |
? |
? |
| 50/60Hz |
B7 |
D7 |
E7 |
F7 |
M7 |
P7 |
U7 |
Q7 |
V7 |
N7 |
R7 |
? |
?/td>
|
|