DZ47LE-63 1P |
1. Application
DZ47LE-63 is applicable to a line of AC 50Hz/60Hz, rated voltage 230V for single pole two-wire, 2-pole or 400V for 3-pole, 3-pole 4-wire, 4-pole and rated current up to 40A. It can protect the line and motor from overload and short circuit. It can also be used for infrequent line conversion and infrequent motor start. It conforms with the standards of IEC61009.
2. Main Technical Parameter
| Type |
DZ47LE-63 |
| Pole |
1P+N, 2P |
3P, 3P+N, 4P |
| Rated current (A) |
6,10,16,20,25,32,40,50,63 |
| Rated voltage (V) |
230 |
400 |
| Rated short circuit breaking capacity Icn(KA) |
6-32A :6 / 40-63: 4.5 |
| Rated residual making/breaking capacity IΔm(A) |
2000 |
| Rated residual action current IΔn(A) |
0.03,0.05,0.1,0.3 |
| Rated residual non-action current IΔno(A) |
0.5IΔn |
3. Applicable conducting wire
| current(A) |
1-6A |
10A |
16,20A |
25A |
32A |
40,50A |
63A |
| Norminal cross section of wire mm2 |
1 |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
4. Residual current breaking time
| In (A) |
IΔn (A) |
Breaking time(s) when equals to rating following |
| IΔn |
2IΔn |
5IΔn |
5,10,20,50,100,200,500a(A) |
IΔtb |
| 6-63 |
0.03, 0.05, 0.1, 0.3 |
0.1 |
0.06 |
0.04 |
0.04 |
0.04 |
5. The over-current protection property
| Ambient Temperature |
Initial Status |
Test Current |
Expected Result |
Expected Result |
Note |
| 30?°C |
Cold position |
1.13In |
t ≥ 1h |
Non-release |
? |
| Carried out immediately after previous test |
1.45In |
t<1h |
Release |
? |
| Cold position |
2.55In |
1s<t<60s
(In ≤ 32A) |
Release |
Current smoothly rises to specified value within 5s |
| Cold position |
2.55In |
1s<t<120s (In>32A) |
Release |
| -5~+40°C |
Cold position |
3In |
t ≥ 0.1s |
Non-release |
Type B |
| Cold position |
5In |
t<0.1s |
Release |
Type B |
| Cold position |
5In |
t ≥ 0.1s |
Non-release |
Type C |
| Cold position |
10In |
t<0.1s |
Release |
Type C |
| Cold position |
10In |
t ≥ 0.1s |
Non-release |
Type D |
| Cold position |
20In |
t<0.1s |
Release |
Type D |