>> contents |
|
JR26 & LR7 Series Thermal Relay
|

JR26 |
JR26 Series Thermal Relay
1. Application JR26 thermal relay is suitable for overload protection of AC motor operated on 8-hours duty or uninterupted duty. The overload protected AC motor with frequency 50Hz, voltage up to 660V, current up to 30A. Several functions provided by these relays are: phase-failure protection, temperature compensation. The product conforms to IEC60947-4-1 stardand.
2. Motion Characteristic: Three-phase Balance Motion Time
| No |
Times of the setting current |
Motion time |
Start condition |
Ambient temperature |
| 1 |
1.05 |
>2h |
Cold state |
20?°C |
| 2 |
1.2 |
<2h |
Heat state
(Following the No.1 test) |
| 3 |
1.5 |
<4min |
| 4 |
7.2 |
10A |
2s<Tp ≤ 10s |
≤ 63A |
Cold state |
| 10 |
4s<Tp ≤ 10s |
>63A |
3. Specification
| Type |
Setting range (A) |
| JR26-25 |
2.4~3.8 |
| 3.8~6 |
| 6~9.3 |
| 8.9~13.5 |
| 13.5~20 |
| 17.4~24 |
| 22~30 |
4. Outline and Mounting Dimension
|

LR7 |
LR7 Series Thermal Relay
1. Application
LR7 thermal relay is suitable for overload protection of AC motor operated on 8-hours duty or uninterupted duty. The overload protected AC motor with frequency 50Hz, voltage up to 660V, current up to 38A. Several functions provided by these relays are: phase-failure protection, temperature compensation. The product conforms to IEC60947-4-1 stardand.
2. Motion Characteristic: Three-phase Balance Motion Time
| No |
Times of the setting current |
Motion time |
Start condition |
Ambient temperature |
| 1 |
1.05 |
>2h |
Cold state |
20?°C |
| 2 |
1.2 |
<2h |
Heat state
(Following the No.1 test) |
| 3 |
1.5 |
<4min |
| 4 |
7.2 |
10A |
2s<Tp ≤ 10s |
≤ 63A |
Cold state |
| 10 |
4s<Tp ≤ 10s |
>63A |
3. Specification
| Type |
Setting range (A) |
| LR7-20 |
0.6~1.11 |
| 1.11~1.66 |
| 2.5~3.7 |
| 1.62~2.5 |
| 3.7~5.6 |
| 5.6~8.4 |
| 8.4~11.9 |
| 11.9~16 |
| 16~23 |
| 23~27 |
| 27~33 |
| 33~38 |