1. Application JRS5 thermal relay is suitable for overload protection of AC motor operated on 8-houres duty or uninterupted duty. The overload protected AC motor with frequency 50Hz, voltage up to 660V, current up to 105A. Several functions provided by these relays are: phase-failure protection, temperature compensation, ON/OFF indication and manual/automatic reset. The product conforms to IEC60947-4-1 stardand.
2. Motion Characteristic: Three-phase Balance Motion Time
| No |
Times of the setting current |
Motion time |
Start condition |
Ambient temperature |
| 1 |
1.05 |
>2h |
Cold state |
20?°C |
| 2 |
1.2 |
<2h |
Heat state (Following the No.1 test) |
| 3 |
1.5 |
<4min |
| 4 |
7.2 |
10A |
2s<Tp ≤ 10s |
≤ 63A |
Cold state |
| 10 |
4s<Tp ≤ 10s |
>63A |
3. Phase-losing Motion Characteristic
| No |
Times of the setting current |
Motion time |
Start condition |
Ambient temperature |
| Any two phases |
Another phase |
| 1 |
1.0 |
0.9 |
>2h |
Cold state |
20?°C |
| 2 |
1.15 |
0 |
<2h |
Heat state (Following the No.1 test) |